init
This commit is contained in:
commit
e1f3d6e0d2
1
.gitignore
vendored
Normal file
1
.gitignore
vendored
Normal file
@ -0,0 +1 @@
|
||||
/.venv
|
111
apc.py
Normal file
111
apc.py
Normal file
@ -0,0 +1,111 @@
|
||||
import subprocess
|
||||
|
||||
def snmp_get(ip, community, oid):
|
||||
command = f"snmpget -v2c -O v -O q -c {community} {ip} {oid}"
|
||||
result = subprocess.run(command, shell=True, capture_output=True, text=True)
|
||||
return result.stdout.strip().strip('"')
|
||||
|
||||
def interpret_flags(state_string):
|
||||
if state_string == "UNKNOWN":
|
||||
return "NMC имеет внутреннюю проблему коммуникации с ИБП."
|
||||
|
||||
flags_description = {
|
||||
1: "Abnormal Condition Present",
|
||||
2: "On Battery",
|
||||
3: "Low Battery",
|
||||
4: "On Line",
|
||||
5: "Replace Battery",
|
||||
6: "Serial Communication Established",
|
||||
7: "AVR Boost Active",
|
||||
8: "AVR Trim Active",
|
||||
9: "Overload",
|
||||
10: "Runtime Calibration",
|
||||
11: "Batteries Discharged",
|
||||
12: "Manual Bypass",
|
||||
13: "Software Bypass",
|
||||
14: "In Bypass due to Internal Fault",
|
||||
15: "In Bypass due to Supply Failure",
|
||||
16: "In Bypass due to Fan Failure",
|
||||
17: "Sleeping on a Timer",
|
||||
18: "Sleeping until Utility Power Returns",
|
||||
19: "On",
|
||||
20: "Rebooting",
|
||||
21: "Battery Communication Lost",
|
||||
22: "Graceful Shutdown Initiated",
|
||||
23: "Smart Boost or Smart Trim Fault",
|
||||
24: "Bad Output Voltage",
|
||||
25: "Battery Charger Failure",
|
||||
26: "High Battery Temperature",
|
||||
27: "Warning Battery Temperature",
|
||||
28: "Critical Battery Temperature",
|
||||
29: "Self Test In Progress",
|
||||
30: "Low Battery / On Battery",
|
||||
31: "Graceful Shutdown Issued by Upstream Device",
|
||||
32: "Graceful Shutdown Issued by Downstream Device",
|
||||
33: "No Batteries Attached",
|
||||
34: "Synchronized Command is in Progress",
|
||||
35: "Synchronized Sleeping Command is in Progress",
|
||||
36: "Synchronized Rebooting Command is in Progress",
|
||||
37: "Inverter DC Imbalance",
|
||||
38: "Transfer Relay Failure",
|
||||
39: "Shutdown or Unable to Transfer",
|
||||
40: "Low Battery Shutdown",
|
||||
41: "Electronic Unit Fan Failure",
|
||||
42: "Main Relay Failure",
|
||||
43: "Bypass Relay Failure",
|
||||
44: "Temporary Bypass",
|
||||
45: "High Internal Temperature",
|
||||
46: "Battery Temperature Sensor Fault",
|
||||
47: "Input Out of Range for Bypass",
|
||||
48: "DC Bus Overvoltage",
|
||||
49: "PFC Failure",
|
||||
50: "Critical Hardware Fault",
|
||||
51: "Green Mode/ECO Mode",
|
||||
52: "Hot Standby",
|
||||
53: "Emergency Power Off (EPO) Activated",
|
||||
54: "Load Alarm Violation",
|
||||
55: "Bypass Phase Fault",
|
||||
56: "UPS Internal Communication Failure",
|
||||
57: "Efficiency Booster Mode",
|
||||
58: "Off",
|
||||
59: "Standby",
|
||||
60: "Minor or Environment Alarm",
|
||||
}
|
||||
|
||||
|
||||
positions = [pos + 1 for pos, char in enumerate(state_string) if char == '1']
|
||||
flags = [flags_description.get(pos, f"Flag {pos} not defined") for pos in positions]
|
||||
|
||||
return ", ".join(flags)
|
||||
|
||||
|
||||
|
||||
oids = {
|
||||
"upsAdvBatteryCapacity": "1.3.6.1.4.1.318.1.1.1.2.2.1.0",
|
||||
"upsAdvBatteryRunTimeRemaining": "1.3.6.1.4.1.318.1.1.1.2.2.3.0",
|
||||
"upsAdvBatteryTemperature": "1.3.6.1.4.1.318.1.1.1.2.2.2.0",
|
||||
"upsAdvOutputLoad": "1.3.6.1.4.1.318.1.1.1.4.2.3.0",
|
||||
"upsBasicStateOutputState": "1.3.6.1.4.1.318.1.1.1.11.1.1.0",
|
||||
"upsBasicIdentModel": "1.3.6.1.4.1.318.1.1.1.1.1.1.0"
|
||||
|
||||
}
|
||||
|
||||
|
||||
def parse_time(time_str):
|
||||
time_parts = time_str.split(":")[-4:]
|
||||
days = int(time_parts[0])
|
||||
hours = int(time_parts[1])
|
||||
minutes = int(time_parts[2])
|
||||
seconds = float(time_parts[3])
|
||||
total_minutes = (days * 24 * 60) + (hours * 60) + minutes + (int(seconds // 60))
|
||||
return total_minutes
|
||||
|
||||
|
||||
for name, oid in oids.items():
|
||||
response = snmp_get('10.31.41.46', 'public', oid)
|
||||
if name == "upsBasicStateOutputState":
|
||||
print(f"{name}: {interpret_flags(response)}")
|
||||
elif name == "upsAdvBatteryRunTimeRemaining":
|
||||
print(f"{name}: {parse_time(response)} minutes")
|
||||
else:
|
||||
print(f"{name}: {response}")
|