apc_snmp_shutdown/apc.py

112 lines
3.9 KiB
Python
Raw Normal View History

2024-08-13 04:17:30 +03:00
import subprocess
def snmp_get(ip, community, oid):
command = f"snmpget -v2c -O v -O q -c {community} {ip} {oid}"
result = subprocess.run(command, shell=True, capture_output=True, text=True)
return result.stdout.strip().strip('"')
def interpret_flags(state_string):
if state_string == "UNKNOWN":
return "NMC имеет внутреннюю проблему коммуникации с ИБП."
flags_description = {
1: "Abnormal Condition Present",
2: "On Battery",
3: "Low Battery",
4: "On Line",
5: "Replace Battery",
6: "Serial Communication Established",
7: "AVR Boost Active",
8: "AVR Trim Active",
9: "Overload",
10: "Runtime Calibration",
11: "Batteries Discharged",
12: "Manual Bypass",
13: "Software Bypass",
14: "In Bypass due to Internal Fault",
15: "In Bypass due to Supply Failure",
16: "In Bypass due to Fan Failure",
17: "Sleeping on a Timer",
18: "Sleeping until Utility Power Returns",
19: "On",
20: "Rebooting",
21: "Battery Communication Lost",
22: "Graceful Shutdown Initiated",
23: "Smart Boost or Smart Trim Fault",
24: "Bad Output Voltage",
25: "Battery Charger Failure",
26: "High Battery Temperature",
27: "Warning Battery Temperature",
28: "Critical Battery Temperature",
29: "Self Test In Progress",
30: "Low Battery / On Battery",
31: "Graceful Shutdown Issued by Upstream Device",
32: "Graceful Shutdown Issued by Downstream Device",
33: "No Batteries Attached",
34: "Synchronized Command is in Progress",
35: "Synchronized Sleeping Command is in Progress",
36: "Synchronized Rebooting Command is in Progress",
37: "Inverter DC Imbalance",
38: "Transfer Relay Failure",
39: "Shutdown or Unable to Transfer",
40: "Low Battery Shutdown",
41: "Electronic Unit Fan Failure",
42: "Main Relay Failure",
43: "Bypass Relay Failure",
44: "Temporary Bypass",
45: "High Internal Temperature",
46: "Battery Temperature Sensor Fault",
47: "Input Out of Range for Bypass",
48: "DC Bus Overvoltage",
49: "PFC Failure",
50: "Critical Hardware Fault",
51: "Green Mode/ECO Mode",
52: "Hot Standby",
53: "Emergency Power Off (EPO) Activated",
54: "Load Alarm Violation",
55: "Bypass Phase Fault",
56: "UPS Internal Communication Failure",
57: "Efficiency Booster Mode",
58: "Off",
59: "Standby",
60: "Minor or Environment Alarm",
}
positions = [pos + 1 for pos, char in enumerate(state_string) if char == '1']
flags = [flags_description.get(pos, f"Flag {pos} not defined") for pos in positions]
return ", ".join(flags)
oids = {
"upsAdvBatteryCapacity": "1.3.6.1.4.1.318.1.1.1.2.2.1.0",
"upsAdvBatteryRunTimeRemaining": "1.3.6.1.4.1.318.1.1.1.2.2.3.0",
"upsAdvBatteryTemperature": "1.3.6.1.4.1.318.1.1.1.2.2.2.0",
"upsAdvOutputLoad": "1.3.6.1.4.1.318.1.1.1.4.2.3.0",
"upsBasicStateOutputState": "1.3.6.1.4.1.318.1.1.1.11.1.1.0",
"upsBasicIdentModel": "1.3.6.1.4.1.318.1.1.1.1.1.1.0"
}
def parse_time(time_str):
time_parts = time_str.split(":")[-4:]
days = int(time_parts[0])
hours = int(time_parts[1])
minutes = int(time_parts[2])
seconds = float(time_parts[3])
total_minutes = (days * 24 * 60) + (hours * 60) + minutes + (int(seconds // 60))
return total_minutes
for name, oid in oids.items():
response = snmp_get('10.31.41.46', 'public', oid)
if name == "upsBasicStateOutputState":
print(f"{name}: {interpret_flags(response)}")
elif name == "upsAdvBatteryRunTimeRemaining":
print(f"{name}: {parse_time(response)} minutes")
else: